JACE 8000 IO R Technical Data
Important technical data:
Maximum expansion
Maximum expansion
- (8) IO-R-34s
- Or (16) IO-R-16s
Power
Power
One IO-R-34 can power four IO-R-16 modules
Common configurations
Common configurations
- Maximum configuration for 2 panels. Shown with maximum of 4 IO-R-16s per IO-R-34
- Maximum configuration for 4 panels
- Maximum configuration for 8 panels
Certificate of conformity
Certificate of conformity
- UL 916
- C-UL
- CE EN 61326-1:2013
- RCM
- FCC part 15, class b
- RoHS2
- REACH
- WEEE
- China ROHS
- Open Energy Management Class 2
Environmental specifications
Environmental specifications
- Operating temperature: -20–60°C
- Storage temperature: -40–85°C
- Humidity: 5%–95% — Noncondensing
- Shipping & vibration: ASTM D4169, Assurance Level II
- MTTF: 10 years+
JACE 8000 IO R Key Features
Introducing an IO solution that makes the next-generation JACE® 8000 more powerful, and your migration path straightforward.
Design simplicity, technical sophistication and more, in both a 16- and 34-point module.
Ease of use:
Ease of use:
Single-tool programming inside the Niagara environment with live debugging.
Enhanced capability:
Enhanced capability:
Ability to set hold time and default states for outputs based on application needs.
Improved flexibility:
Improved flexibility:
Operates over an RS485 network and can be installed anywhere. Multiple modules can be combined so each JACE® 8000 can command more than 250 points of IO.
Minimal wiring labor:
Minimal wiring labor:
Quick three-step process when moving from NDIO to the JACE® 8000.